Journal of South China University of Technology(Natural Science Edition) ›› 2004, Vol. 32 ›› Issue (3): 10-14.

Previous Articles     Next Articles

Removing of Moisture Load in Cooling Ceiling Air-conditioning System by Rotary Dehumidifier

Ding Yun-fei1 Ding Jing1 Wang Zhuo-yue1 Yang Xiao-xi2    

  1. 1.Key Lab.of Enhanced Heat Transfer and Energy Conservation of the Ministry of Education‚South China Univ.of Tech.‚
    Guangzhou510640‚Guangdong‚China;2.Dept.of Chemistry‚Dongguan Univ.of Tech.‚Dongguan523106‚Guangdong‚China
  • Received:2003-09-08 Online:2004-03-20 Published:2015-09-08
  • Contact: 丁云飞(1967-)‚男‚副教授‚博士研究生‚主要从事暖通空调及强化传热技术研究. E-mail:Dingyf@126.com
  • About author:丁云飞(1967-)‚男‚副教授‚博士研究生‚主要从事暖通空调及强化传热技术研究.

Abstract: The demands and schemes for the moisture load disposal in cooling ceiling air-conditioning sys-tems by using fresh air were investigated‚reaching the conclusion that adsorption dehumidification is better than cooling dehumidification.Experimental results of the moisture load removing by rotary de-humidifier and the feasibility of implementation schemes show that‚in summer‚the rotary dehumidifier can satisfy the system demands when the outdoor air temperature and humidity are respectively lower than30℃ and80% besides office buildings‚and that‚in the high-temperature and high-humidity areas‚the rotary dehumidifier can satisfy the demand for indoor humidity and the demand for low humidity by the head surface cooler preprocessing of the fresh air.Moreover‚the indoor relative humidity can be controlled by regulating the regeneration temperature and the fresh air flowrate of rotary dehumidifier.

Key words: rotary dehumidifier, cooling ceiling air-conditioning system, moisture load

CLC Number: