华南理工大学学报(自然科学版) ›› 2015, Vol. 43 ›› Issue (12): 71-76,84.doi: 10.3969/j.issn.1000-565X.2015.12.010

• 动力与电气工程 • 上一篇    下一篇

水颗粒作用下火灾烟气层沉降的数值模拟

唐智 方正 袁建平 王骏横   

  1. 武汉大学 土木建筑工程学院,湖北 武汉 430072
  • 收稿日期:2015-02-21 修回日期:2015-05-29 出版日期:2015-12-25 发布日期:2015-11-01
  • 通信作者: 袁建平(1981-),男,副教授,博士,主要从事建筑防火技术研究. E-mail:jpyuan@whu.edu. cn
  • 作者简介:唐智(1985-),男,讲师,博士,主要从事建筑防火技术研究. E-mail:zhi_tang@126.com
  • 基金资助:
    中国博士后科学基金资助项目(2014M562060);武汉大学中央高校基本科研业务费专项资金资助项目(2042014kf0009)

Numerical Simulation for the Downward Smoke Displacement under the Effect of Water Droplets

Tang Zhi Fang Zheng Yuan Jian-ping Wang Jun-heng   

  1. School of Civil Engineering,Wuhan University,Wuhan 430072,Hubei,China
  • Received:2015-02-21 Revised:2015-05-29 Online:2015-12-25 Published:2015-11-01
  • Contact: 袁建平(1981-),男,副教授,博士,主要从事建筑防火技术研究. E-mail:jpyuan@whu.edu. cn
  • About author:唐智(1985-),男,讲师,博士,主要从事建筑防火技术研究. E-mail:zhi_tang@126.com
  • Supported by:
    Supported by the China Postdoctoral Science Foundation(2014M562060)

摘要: 基于火灾双层模型思想及基本物理定律,通过分析单个水颗粒与热气流的相互作用,研究水颗粒群对火灾烟气层的影响,建立了水颗粒作用下火灾烟气层沉降的数学模型,模型与实验值的对比误差为 ±0. 3 m. 利用该模型模拟研究发现:增大喷头流量速率、减小水颗粒喷射夹角、减小水颗粒粒径会加剧烟气层沉降;在同一喷水条件下,低温、薄烟气层更易于沉降,当烟气层厚度薄于某一临界值时,烟气沉降距离会大幅度增加;常用的12. 7mm 喷淋喷头的工作压力不宜大于 20 m. 该模型可有效缓解喷水对实际火灾烟气层的沉降作用.

关键词:  喷头, 水颗粒, 火灾, 烟气, 沉降

Abstract: Based on the basic physic laws and the idea of two-zone model of fire,a mathematical model of the downward smoke displacement in fire under the effect of water droplets is constructed by analyzing the interaction between a single droplet and hot air flow and by investigating the impact of water droplets on the smoke layer of fire. Then,the constructed model is compared with the measured data,finding that the error of the constructed model is ±0. 3 m. The modeling results show that (1) increasing the flow rate of nozzles and decreasing the size and spray angle of water droplets can increase the downward smoke displacement; (2) under the same spray condition,the downward smoke displacement is easy to occur in a thin and low-temperature fire smoke layer; (3) when the thick-ness of the smoke layer is less than a critical value,the downward smoke displacement distance will greatly increase;and (4) the operation pressure of the commonly-used sprinkler nozzle with a 12. 7 mm orifice should not be larger than 20 m,so that the impact of the water droplets on the downward smoke displacement can be effectively reduced.

Key words: nozzles, water droplet, fire, smoke, downward displacement