Journal of South China University of Technology(Natural Science Edition) ›› 2021, Vol. 49 ›› Issue (2): 17-24,67.doi: 10.12141/j.issn.1000-565X.200341

Special Issue: 2021年能源、动力与电气工程

• Energy, Power & Electrical Engineering • Previous Articles     Next Articles

Concentration Closed-Loop Control of Dry Electrostatic Precipitator in a 1 000 MW Coal-Fired Unit

HAO Yongsheng1 WANG Zhongwei1 ZHU Xiaojin2 SU Zhigang1 ZHAO Gang1 YIN Jie3   

  1. 1. School of Energy and Environment,Southeast University,Nanjing 210096,Jiangsu,China; 2. Zhejiang Zheneng Taizhou Second Electric Power Generation Co. ,Ltd. ,Taizhou 318000,Zhejiang,China; 3. Nanjing Reason Information Technology Co. ,Ltd. ,Nanjing 210038,Jiangsu,China
  • Received:2020-06-22 Revised:2020-11-27 Online:2021-02-25 Published:2021-02-01
  • Contact: 苏志刚 ( 1979-) ,男,博士,副教授,主要从事能源动力系统智能诊断与优化控制研究。 E-mail:zhigangsu@seu.edu.cn
  • About author:郝勇生(1978-) ,男,博士,副教授,主要从事火电机组控制及运行优化研究。E-mail: haoys@seu.edu.cn
  • Supported by:
    Supported by the National Natural Science Foundation of China ( 52076037)

Abstract: Closed-loop control method of electrostatic precipitator outlet dust concentration was studied to solve the problems of high energy consumption of dry electrostatic precipitator in 1000 MW coal-fired units and the failure to achieve closed-loop control of concentration. Firstly,for dry electrostatic precipitator with a five-field structure,a concentration control method combining feedforward control of the first three-stage electric fields and closed-loop control of the last two-stage electric field was proposed. The IMC-PID parameter setting method was used to set the PID ( Proportional Integral Derivative) controller parameters,and a disturbance observer was added to the PID controller to enhance the anti-disturbance ability of the system. Finally,the method of fuzzy weighted switching was used to achieve smooth switching between the control functions of each load point model. The simulation and experimental results show that the proposed control method can realize the fixed value control of electrostatic precipitator outlet dust concentration and has good performance.

Key words: ESP, closed-loop control, IMC-PID, disturbance observer, fuzzy weight

CLC Number: