Effect of Inlet Parameters on Performance of Regenerator Under Winter Conditions

Li Yong-cun  Chen Guang-ming  Zhang Shao-zhi  Tang Li-ming   

  1. Institute of Refrigeration and Cryogenics,Zhejiang University,Hangzhou 310027,Zhejiang,China
  • Received:2011-05-18 Revised:2011-10-08 Online:2012-01-25 Published:2011-12-01
  • Contact: 陈光明(1958-) ,男,教授,博士生导师,主要从事低品位能源利用等研究.E-mail:gmchen@zju.edu.cn E-mail:yongcun_li@ sina.com
  • About author:李永存(1976-) ,男,博士生,讲师,主要从事无霜空气源热泵研究.
  • Supported by:

    国家自然科学基金资助项目( 50976097)

Abstract:

As there have no sufficient performance data of the regenerators under winter conditions,the corresponding design and operation of regenerators are difficult to perform. In order to solve this problem,an experimental system is established to analyze the effects of inlet air and solution parameters on the performance of regenerators under winter conditions,and the corresponding laws are drawn when aqueous LiCl is used as the regeneration solution. The results indicate that the outlet air temperature,the outlet solution temperature and the outlet air humidity ratio all increase with the inlet solution temperature,the inlet air temperature,the inlet solution mass flowrate and the inlet air humidity ratio,while they all decrease with the increase in the inlet air mass flowrate,and that,with the increase in LiCl mass fraction,both the outlet air temperature and the outlet solution temperature increase but the outlet air humidity ratio decreases. In addition,a correlation of regeneration rate and regeneration efficiency is also proposed,which is suitable for the design,operation and performance investigation of regenerators under winter
conditions.

Key words: regenerator, winter condition, inlet parameter, outlet parameter, regeneration performance