Journal of South China University of Technology (Natural Science Edition) ›› 2017, Vol. 45 ›› Issue (10): 46-52,61.doi: 10.3969/j.issn.1000-565X.2017.10.007

Previous Articles     Next Articles

Transient Overvoltage Simulation of Medium-Voltage Cable Collector System in Offshore Wind Farm

LIU Gang1 JIANG Xiao-feng1 GUO Ya-xun1 XIN Yan-li1 LIANG Jia-hao1 ZHOU Lu1 ZHNEG Ming2   

  1. 1.School of Electric Power,South China University of Technology,Guangzhou 510640,Guangdong,China; 2.Guangdong Electric Power Design Institute Co.Ltd.of China Energy Engineering Group,Guangzhou 510663,Guangdong,China
  • Received:2017-03-03 Revised:2017-04-18 Online:2017-10-25 Published:2017-09-01
  • Contact: 刘刚(1969-),男,博士,副教授,主要从事智能高压电网、过电压及其防护、电力设备外绝缘、海底电缆优化评估研究. E-mail:liugang@scut.edu.cn
  • About author:刘刚(1969-),男,博士,副教授,主要从事智能高压电网、过电压及其防护、电力设备外绝缘、海底电缆优化评估研究.
  • Supported by:
    Supported by the National Natural Science Foundation of China(51477054)

Abstract: In order to reveal the mechanism of how the re-ignition of a vacuum circuit breaker in an offshore wind farm causes the damage of the insulation of the generators with step-up transformers,the high-frequency modeling and the analysis of the vacuum circuit breaker are performed in this paper.First,a simplified simulation model of the medium-voltage cable collector system PSCAD/EMTDC for the offshore wind farms is constructed by using a self-defined vacuum circuit breaker model.Then,the effects of the re-ignition characteristics of the circuit breaker,the initial phase angle of switching and the cable length on the transient overvoltage on the high voltage (HV) side of the generators with the step-up transformers and the re-ignition number are investigated.Simulation results show that the dielectric recovery strength of the three characteristic parameters of the circuit breaker has the greatest in- fluence on the transient overvoltage and the re-ignition number,and that,when the initial phase angle of switching is 45° and the re-ignition phenomenon caused by the interruption of an inductive load circuit breaker occurs,the overvoltage reaches the maximum and its amplitude and steepness are up to 3. 26p. u.and 12. 46p. u.respective- ly.Finally,the scheme of installing the series of choking coils,the parallel small capacitor and the overvoltage pro- tection device of zinc oxide arrester on the HV side of the generators with the step-up transformers at the same time is proposed.Simulation results show that,after the overvoltage protection device is installed,the overvoltage ampli- tude and steepness as well as the re-ignition number are effectively suppressed.

Key words: offshore wind farm, vacuum circuit breaker model, re-ignition characteristic, transient overvoltage, electromagnetic transient simulation, choking coil, zinc oxide arrester