华南理工大学学报(自然科学版) ›› 2011, Vol. 39 ›› Issue (4): 156-162.doi: 10.3969/j.issn.1000-565X.2011.04.027

• 土木建筑工程 • 上一篇    

钢-混凝土连续组合梁非张拉预应力技术的关键参数分析

吴丽丽1,2 聂建国2   

  1. 1.中国矿业大学(北京) 深部岩土力学与地下工程国家重点实验室,北京 100083;2.清华大学 土木工程系//土木工程安全与耐久教育部重点实验室,北京100084
  • 收稿日期:2010-04-21 修回日期:2010-08-30 出版日期:2011-04-25 发布日期:2011-03-01
  • 通信作者: 吴丽丽(1977-),女,博士,副教授,主要从事结构工程研究 E-mail:jennywll@163.com
  • 作者简介:吴丽丽(1977-),女,博士,副教授,主要从事结构工程研究
  • 基金资助:

    国家自然科学基金资助项目(50778103,50808110);中国博士后科学基金资助项目(20080430042)

Analysis of Key Parameters of Non-Tension Prestressing Technology for Continuous Steel-Concrete Composite Beams

 Wu Li-li1,2  Nie Jian-guo2   

  1. 1.State Key Laboratory for Geomeehanics and Deep Underground Engineering,China University of Mining and Technology(Beijing),Beijing 100083,China;2.Department of Civil EngineeringfKey Laboratory of Civil Engineering Safety and Durability of the Education of Ministry,Tsinghua University,Beijing 100084,Chin
  • Received:2010-04-21 Revised:2010-08-30 Online:2011-04-25 Published:2011-03-01
  • Contact: 吴丽丽(1977-),女,博士,副教授,主要从事结构工程研究 E-mail:jennywll@163.com
  • About author:吴丽丽(1977-),女,博士,副教授,主要从事结构工程研究
  • Supported by:

    国家自然科学基金资助项目(50778103,50808110);中国博士后科学基金资助项目(20080430042)

摘要: 通过对2-5跨非张拉预应力连续组合梁各受力阶段的分析,研究了配重大小、配重施加的合理范围以及负弯矩区后浇混凝土长度等非张拉预应力技术中一些关键参数的设计计算方法,并初步探讨了卸除配重后,在使用阶段非张拉预应力连续组合梁负弯矩区裂缝宽度及梁跨中变形的计算方法,提出因实施非张拉预应力技术而引起的反向挠度,可通过将卸除配重的反向荷载转化为满跨均布"等效"荷载,然后计算该"等效"荷载作用下的挠度而得到.结果表明,采用这种"等效"荷载方法计算得到的挠度最大相对误差不超过15%,能满足实际工程的精度要求.

关键词: 钢-混凝土连续组合梁, 非张拉预应力技术, 负弯矩区, 配重, 裂缝宽度, 变形

Abstract:

By analyzing the loading stages of the continuous steel-concrete composite beams with 2-5 spans,some key parameters of the non-tension prestressing technology of the composite beams,such as the counterweights and their arrangement,as well as the post-cast length of concrete in the negative-moment region,are investigated.Then,the calculation methods of crack width in the negative-moment region and mid-span deformation of the composite beams are discussed after the removal of the counterweights.It is suggested that the reverse deflection induced by the non-tension prestressing can be obtained through two steps,namely,converting the reverse loads resulting from weight removing to the full-span uniform "equivalent" ones,and then calculating the deflections under the "equivalent" loads.With this two-step method,the requirements of practical engineering are satisfied well,and the maximum relative error of deflection keeps within 15%.

Key words: continuous steel-concrete composite beam, technology of non-tension prestressing, negative-moment moment region, weights, crack width, deformation