华南理工大学学报(自然科学版) ›› 2008, Vol. 36 ›› Issue (2): 112-116.

• 动力与电气工程 • 上一篇    下一篇

立式蒸发式冷凝器的性能研究与强化实验

吴治将 朱冬生 赵强 涂爱民   

  1. 华南理工大学 传热强化与过程节能教育部重点实验室, 广东 广州 510640
  • 收稿日期:2007-03-20 出版日期:2008-02-25 发布日期:2008-02-25
  • 通信作者: 吴治将(1979-),男,博士生,主要从事传热与节能研究. E-mail:wzj710@163.com
  • 作者简介:吴治将(1979-),男,博士生,主要从事传热与节能研究.
  • 基金资助:

    教育部新世纪优秀人才支持计划项目(NCET040826)

Experimental Investigation into Performance and Enhancement of Vertical Evaporative Condenser

Wu Zhi-jiang  Zhu Dong-shen  Zhao Qiang  Tu Ai-ming   

  1.  Key Laboratory of Enhanced Heat Transfer and Energy Conservation of the Ministry of Education, South China University of Technology, Guangzhou 510640, Guangdong, China
  • Received:2007-03-20 Online:2008-02-25 Published:2008-02-25
  • Contact: 吴治将(1979-),男,博士生,主要从事传热与节能研究. E-mail:wzj710@163.com
  • About author:吴治将(1979-),男,博士生,主要从事传热与节能研究.
  • Supported by:

    教育部新世纪优秀人才支持计划项目(NCET040826)

摘要: 利用竖直有机玻璃管建立立式蒸发式冷凝器性能测试实验平台,测试了进口风速、管高度、传热温差及插入螺旋线对冷凝器传热性能的影响.结果表明:在一定传热温差下,舍伍德数与液膜雷诺数近似呈线性关系,当插入螺旋线后近似呈二次曲线关系;进口风速控制在3.3m/s以下可防止液泛现象的发生;存在着一个最佳换热管的高度范围(0.8~0.9m),在该范围内出口空气的相对湿度最大;螺旋线线径与换热管内径之比在0.06~0.29之间时,可以起到明显的强化传热作用,使舍伍德数提高15%以上.

关键词: 竖管, 蒸发式冷凝器, 传热性能, 强化, 下降液膜

Abstract:

In this paper, a device for testing the performance of evaporative condenser with a vertical plexiglas tube was built up, and the influences of the inlet velocity, the tube height, the heat-transfer temperature difference and the spiral insert on the heat transfer performance of the proposed evaporative condenser were investigated. It is found that, at a certain temperature difference, the relationship between the Sherwood number and the Reynolds number of the falling liquid film is approximately linear, and takes on the form of a quadratic curve in the condition of spiral inserts, that an inlet velocity under 3.3 m/s may prevent the liquid from flooding, that there is an optimal tube height range of 0. 8 to 0. 9 m where the outlet air possesses the largest relative humidity, and that the heat transfer is greatly enhanced and the Sherwood number increases by more than 15% when the ratio of spiral insert diameter to tube diameter ranges from 0. 06 to 0. 29.

Key words: vertical tube, evaporativecondenser, heat transfer performance, enhancement, falling liquid film