Lifespan Assessment of 110kV XLPE Cable Based on Isothermal Relaxation Current Method and Stepwise Voltage Method

Expand
  • 1. School of Electric Power,South China University of Technology,Guangzhou 510640,Guangdong,China;2. Transmission Department,Guangzhou Power Supply Bureau Co. ,Ltd. ,Guangzhou 510310,Guangdong,China
刘刚(1969-),男,博士,副教授,主要从事智能高压电网、过电压及其防护、电力设备外绝缘研究.

Received date: 2015-04-21

  Revised date: 2015-07-07

  Online published: 2015-11-01

Supported by

Supported by the National High-Tech R&D Program of China(863 Program)(2015AA050201),the National Natural Science Foundation of China(51477054) and the Science and Technology Project Item of Guangdong Province(2013B010405002)

Abstract

Short and long samples from the cables running for over twenty years were cut out. Then,the short samples as well as the long samples before and after the electric heating process were tested by means of the isothermal
relaxation current method. The results show that the long samples have a larger aging factor because they have cable
joints,which means that the cable joints constitute the weak link in the cables,and the joints under the electric
heating process are easier to get aging. After the electric heating process,the aging factor of the long samples increases due to the increase of their internal defects,which means that the electric heating process can aggravate the
aging degree of the cables. From the voltage-endurance tests,it is found from the voltage-endurance tests that the
residual life of the samples ranges from ten to twenty years,which is consistent with the expected life in their design. Thus,it comes to the conclusion that the XLPE cable can be more comprehensively judged by combining the
isothermal relaxation current method with the stepwise voltage-endurance method,which means that the aging degree and the residual life can be respectively assessed by using both methods.

Cite this article

Liu Gang Jin Shang-er Zhao Lu Wu Liang Liang Zi-peng Huang Jia-sheng . Lifespan Assessment of 110kV XLPE Cable Based on Isothermal Relaxation Current Method and Stepwise Voltage Method[J]. Journal of South China University of Technology(Natural Science), 2015 , 43(12) : 41 -47 . DOI: 10.3969/j.issn.1000-565X.2015.12.006