Research on Energy Saving for Clean Air Conditioning System Based on Harmonic Response Method
Received date: 2012-12-07
Revised date: 2013-09-04
Online published: 2013-11-19
Supported by
国家科技支撑计划项目(2011BAG07B05-5);广东省科技计划项目(2012A010800039, 2012A010800024)
According to the characteristics of the climate in a zone with hot summer and warm winter,a physicalmodel of a clean room was built.Then,based on the harmonic response method,a numerical calculation of thehourly cooling and moisture load in the modeled clean room with a clean air conditioning system was carried out.Moreover,the effects of the building envelope and the hydrothermal process on the hourly cooling load were ana-lyzed,with the results being finally compared with the actual operation data.It is found that (1) the exterior win-dow shades are of great energy- saving potential,with an indoor hourly cooling load reduction being up to 13.6%;(2) under the same external conditions,the dedicated outdoor air system is superior to the primary return air sys-tem,with a maximum energy- saving rate being up to 38.3%; and (3) the average calculation error of cooling loadis only 10%,which means that the established physical model is reliable.
Ye Can- tao Ma Wei- bin Liu Jin- ping Liu Xue- feng . Research on Energy Saving for Clean Air Conditioning System Based on Harmonic Response Method[J]. Journal of South China University of Technology(Natural Science), 2013 , 41(12) : 81 -89 . DOI: 10.3969/j.issn.1000-565X.2013.12.014
/
| 〈 |
|
〉 |