Journal of South China University of Technology (Natural Science Edition) ›› 2017, Vol. 45 ›› Issue (10): 62-70.doi: 10.3969/j.issn.1000-565X.2017.10.009

• Power & Electrical Engineering • Previous Articles     Next Articles

Precise Modeling and Coordinate Control of Unified Power Quality Conditioner

XU Xiao-gang1,2 XIE Yun-xiang1 WANG Ying-pin1 LI Lan-fang2 ZENG Zhi-wu1 ZHANG Xiao-yu1   

  1. 1.School of Electric Power,South China University of Technology,Guangzhou 510640,Guangdong,China; 2.Electric Power Research Institute of Guangdong Power Grid Co.,Ltd.,Guangzhou 510080,Guangdong,China
  • Received:2016-12-14 Revised:2017-03-13 Online:2017-10-25 Published:2017-09-01
  • Contact: 王映品(1985-),男,博士生,主要从事电能质量治理、电力电子换流技术研究. E-mail:wangyingppp@126.com
  • About author:徐晓刚(1982-),男,高级工程师,主要从事配网电能质量、安全运行与控制研究. E-mail:444217306@qq.com
  • Supported by:
     Supported by the National Natural Science Foundation of China(51577074)

Abstract: In the modeling process of a unified power quality conditioner (UPQC),a series unit model and a pa- rallel unit model are separately constructed in general,and an idealized series transformer is applied.In addition,the interaction between the series unit and the parallel unit has been rarely analyzed.In this paper,a precise mathematical model of the UPQC is constructed by using an equivalent transformer model,which integrates the se- ries unit with the parallel unit.Then,the interaction between a series inverter and a parallel inverter is analyzed,and the corresponding interaction mechanism is obtained.Furthermore,a coordinate control method of the UPQC is proposed based on the unity power factor (UPF) detection method.Simulation and experimental results prove that the proposed method can help the UPQC achieve a better compensation effect,thus verifying the correctness of the constructed mathematical model and the obtained interaction mechanism.

Key words: unified power quality conditioner, equivalent transformer model, precise modeling, unity power fac- tor detection method, coordinated control

CLC Number: