Improved Harmonic Current Detection for Three-Phase Four-Wire Active Power Filter
Received date: 2014-04-11
Revised date: 2014-08-23
Online published: 2014-11-17
Supported by
广东省教育部产学研结合项目(2011B090400136)
王裕 谢运祥 . 改进的三相四线制有源电力滤波器谐波电流检测[J]. 华南理工大学学报(自然科学版), 2014 , 42(12) : 112 -119 . DOI: 10.3969/j.issn.1000-565X.2014.12.017
Accurate and fast harmonic current detection plays an important role in determining the compensationperformance of active power filters.In this paper,an improved three-phase four-wire harmonic current detectionmethod is proposed by combining the traditional instantaneous reactive power theory with the FBD method.In thismethod,the algorithm complexity is reduced by cutting the unnecessary separation link of the zero-sequence cur-rent,and the matrix operations caused by the coordinate transformation in the traditional instantaneous reactivepower method are also reduced,thus improving the real-time and dynamic performance of the harmonic current de-tection.Moreover,the zero-axiscurrent is compensated separately and the balance control of upper and lower capac-itor voltages is conducted,so as to ensure the applicability of the active power filter of three-phase four-wire capaci-tors.In order to reduce the hysteresis error caused by the low-pass filter during the sampling and calculation and toimprove the harmonic detection accuracy,an improved moving average algorithm is adopted to replace the low-passfilter.Finally,the feasibility and superiority of the proposed method are verified through the simulation and experi-ment in a three-phase four-wire active power filter.
/
| 〈 |
|
〉 |